Backup power

UPS runtime

Estimate UPS runtime from actual battery energy and load, with a check against its output power rating.

Your inputs

Wh

Nominal stored energy in Wh. A UPS power rating in VA is not battery capacity.

W

The combined average output power required by your devices.

W

The continuous output power limit in watts, not volt-amperes.

%

Share of nominal battery energy available for this discharge.

%

Output energy divided by input energy. Enter a percentage above 0 and up to 100.

W

Extra power drawn on the battery’s DC side. Do not count it again if it is already included in efficiency.

Enter numbers without thousands separators. A comma or a full stop can be used for decimals.

Your estimate

Updates as you type
Estimated runtime
0.88h
Usable battery energy
162 Wh
Battery-side power draw
183.47 W
UPS load
25 %

An estimate based on your inputs. Example values are not current tariffs or equipment recommendations.

Use battery energy in Wh, not a VA rating. Check the manufacturer’s runtime curve for the actual UPS and load.

How it works

The energy model follows battery runtime, then compares connected load with the UPS continuous watt rating. Volt-amperes are not a measure of stored energy.

Hours = usable Wh ÷ (load W ÷ efficiency + extra standby W). Load % = load W ÷ rated W × 100.

Worked example

For 216 Wh, 75% usable capacity, 150 W load, 85% efficiency and 7 W extra draw, runtime is about 0.88 hours, or 53 minutes. A 600 W UPS is at 25% load.

What to keep in mind

  • Enter the battery pack energy in Wh, not the UPS VA rating.
  • Manufacturer runtime curves are preferable for final equipment selection, especially at high loads.

Reference sources

References explain the underlying concepts. The tool uses the simplified method stated above.