Battery runtime

Estimate battery runtime from stored energy, usable capacity, load, efficiency and extra standby draw.

Your inputs

Wh

Nominal stored energy in Wh. A UPS power rating in VA is not battery capacity.

W

The combined average output power required by your devices.

%

Share of nominal battery energy available for this discharge.

%

Output energy divided by input energy. Enter a percentage above 0 and up to 100.

W

Extra power drawn on the battery’s DC side. Do not count it again if it is already included in efficiency.

Enter numbers without thousands separators. A comma or a full stop can be used for decimals.

Your estimate

Updates as you type
Estimated runtime
7.75h
Usable battery energy
900 Wh
Battery-side power draw
116.11 W

An estimate based on your inputs. Example values are not current tariffs or equipment recommendations.

Runtime assumes a steady load and fixed efficiency. Battery age, temperature, discharge rate and protection cut-offs can change it.

How it works

Usable stored energy is divided by the power drawn from the battery. Load is adjusted for conversion losses; any extra DC standby power is added separately.

Hours = usable Wh ÷ (load W ÷ efficiency + extra standby W).

Worked example

A 1,000 Wh battery with 80% usable energy, a 100 W load, 90% efficiency and no extra standby draw has an estimated runtime of 7.2 hours.

What to keep in mind

  • Efficiency and usable capacity are entered as percentages; the formula uses their fractional values.
  • A steady-load estimate does not model battery chemistry, temperature or ageing.

Reference sources

References explain the underlying concepts. The tool uses the simplified method stated above.