Backup power

Inverter sizing

Estimate continuous and peak inverter power requirements from simultaneous loads and a sizing margin.

Your inputs

W

Sum of loads that may operate at the same time.

W

Total power during the assumed start-up event, including other running loads.

%

Extra percentage above continuous load; applied to the continuous requirement.

Enter numbers without thousands separators. A comma or a full stop can be used for decimals.

Your estimate

Updates as you type
Continuous power requirement
1,000W
Peak power requirement
1,800 W

An estimate based on your inputs. Example values are not current tariffs or equipment recommendations.

Check both continuous and surge ratings, surge duration, battery current and equipment compatibility before selecting an inverter.

How it works

The sizing margin is applied to continuous combined load. The required peak rating is the greater of this continuous requirement and your total simultaneous start-up peak.

Continuous W = running W × (1 + margin). Peak W = the greater of continuous W and total surge W.

Worked example

For an 800 W continuous load, a 25% margin gives 1,000 W continuous capacity. If the total simultaneous peak is 1,800 W, the peak requirement remains 1,800 W.

What to keep in mind

  • Enter total simultaneous peak, including other running devices; do not add the same load twice.
  • Surge duration, battery current, wiring and equipment compatibility need separate verification.

Reference sources

References explain the underlying concepts. The tool uses the simplified method stated above.